5925-01-197-4690 Item Description: Circuit Breaker | 5925 | 011974690 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Jc2s-A8-Eb-01-D-A-30-20 | 5 | 9 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | ||
ABXD | BUSHING LENGTH | 0.098 INCHES MINIMUM AND 0.162 INCHES MAXIMUM |
ADAQ | BODY LENGTH | 1.968 INCHES MINIMUM AND 2.032 INCHES MAXIMUM |
ADAT | BODY WIDTH | 1.468 INCHES MINIMUM AND 1.532 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.528 INCHES MINIMUM AND 1.592 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.718 INCHES MINIMUM AND 0.782 INCHES MAXIMUM |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.628 INCHES MINIMUM AND 1.692 INCHES MAXIMUM |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.718 INCHES MINIMUM AND 0.782 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.898 INCHES MINIMUM AND 1.962 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 2 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 22.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 4 QUICK DISCONNECT, MALE |