MRC | Criteria | Characteristic |
---|---|---|
AAQL | ||
ADAQ | BODY LENGTH | 2.418 INCHES MINIMUM AND 2.482 INCHES MAXIMUM |
ADAT | BODY WIDTH | 1.718 INCHES MINIMUM AND 1.782 INCHES MAXIMUM |
ADAU | BODY HEIGHT | 1.811 INCHES MINIMUM AND 1.875 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.923 INCHES MINIMUM AND 0.987 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.093 INCHES MINIMUM AND 0.157 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 2 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 CLIP |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRK | AUXILIARY TRIP COIL VOLTAGE TYPE AND RATING IN VOLTS | 220.0 AC NOMINAL FIRST LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SECOND LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP W/REMOTE TRIP FEATURE FIRST LOCATION |
CQQC | TRIP RELEASE DUTY CYCLE | CONTINUOUS FIRST LOCATION |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 5 TAB, SOLDER LUG |
JB2-758 | JB22 | JB220S | JB2-758 |
JB200 | JB220UUF | JB2 A3 CB A 15 3 | JB20-403 |
JB2-02-J | JB220S | JB20K-240 | JB21250-1 |
JB220UUF | JB2200W | JB2 A2 A 20 3 | JB2-02-J |