MRC | Criteria | Characteristic |
---|---|---|
ADAQ | BODY LENGTH | 1.552 INCHES MINIMUM AND 1.572 INCHES MAXIMUM |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
APNQ | III ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 0.700 MINIMUM ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND EXPLOSION PROOF AND FUNGUS RESISTANT AND MOISTURE RESISTANT AND VIBRATIONPROOF |
AAQL | BODY STYLE | SINGLE POLE TYPE |
AKPX | POLE QUANTITY | 3 |
CMLP | THREAD QUANTITY PER INCH | 32 |
AFJN | III FRAGILITY FACTOR | MODERATELY RUGGED |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
ADAT | BODY WIDTH | 1.844 INCHES MINIMUM AND 1.906 INCHES MAXIMUM |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.865 INCHES MINIMUM AND 0.885 INCHES MAXIMUM |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THD BUSHING |
FREQ | FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 75.0 MILLIAMPERES AC ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0.375 INCHES |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
ABXD | BUSHING LENGTH | 0.365 INCHES MINIMUM AND 0.385 INCHES MAXIMUM |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BBRG | III STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
TTQY | TERMINAL TYPE AND QUANTITY | 6 WIRE HOOK |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
THSD | THREAD SERIES DESIGNATOR | UNEF |
ADTV | CASE MATERIAL | METAL |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.400 NOMINAL AT 150 PCT AND 0.150 NOMINAL AT 200 PCT AND 0.035 NOMINAL AT 300 PCT AND 0.004 NOMINAL AT 1000 PCT ALL LOCATIONS |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.690 INCHES MINIMUM AND 1.710 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.615 INCHES MINIMUM AND 0.635 INCHES MAXIMUM |